CHMP(3Pb)3-1 24kV 95-240

Transition joint
for 3 lead sheath cables to three 1-core polymeric cables
Art. no.
197633
More Information
Product family CHMP(3Pb)3-1
Product family CHMP(3Pb)3-1
Main description Transition joint
Sub description for 3 lead sheath cables to three 1-core polymeric cables
Family description Hybrid transition joints CHMP(3Pb)3-1 for transition to three 1-core polymericinsulated cables are suitable for all 3 lead sheath cables up to 36 kV. The scope of application can be reduced by an appropriate padding set for the mass-impregnated paper cable. Suitable for compression connectors.
Optional accessory Compression connectors (see Connecting technology)
Characteristics Reliable stress control due to flexible silicone stress control elements, Wide cross-section range, Quick, safe and easy assembly, Ready for immediate operation
Applications Indoor, Outdoor, Underground, Water, Installation ducts, Ductwork
More Information
Voltage levels U0/U (Um) 12/20 (24) kV - 12,7/22 (24) kV
Test standards DIN VDE 0278-629-2
Diameter Connector 24kV max 34 mm
Length Connector 24kV max 150 mm
Length L 1200 mm
Diameter over core insulation after removal of the outer conductive layer min 19,9 mm
Nominal cross section 24 kV min 95 mm²
Nominal cross section 24 kV max 240 mm²
More Information
Delivery scope Spreader cap, Thick wall heat shrinkable outer tube with hot melt adhesive, Oil barrier tubing, Silicone field control elements, Earthing wire, Heat shrinkable tubes, Copper braid tape, Assembly material, Pressure spring, Field control filling tape (blue), Sealing tape, Fire protection wrapping, Assembly instructions
Shelf life description Unlimited shelf life
Country of origin Germany
Customs tariff number 39269097
EAN/GTIN 4010311051703
Alternate quantity 1 1 1
Alternative unit of measure Piece Carton Pal. OW
Base quantity 1 1 12
Base unit of measure Piece Piece Piece
Lenght (mm) 873 873 1200
Width (mm) 380 380 800
Height (mm) 187 187 1130
Net weight (kg) 6,013 6,013 72,156
Gross weight (kg) 6,013 6,013 90,356