CHEP(3Pb)-3I 24kV 16-35

Indoor cable termination
for 3 lead sheath cables from 24 to 36 kV (MIND)
Art. no.
197555
More Information
Main description Indoor cable termination
Sub description for 3 lead sheath cables from 24 to 36 kV (MIND)
Family description Hybrid cable terminations CHEP(3Pb)-3I are suitable for 3 lead sheath cables from 24 to 36 kV (for MIND cables only). Suitable for compression and screw cable lugs.
Notes For cables with draining compound, please contact us.
Optional accessory Cable lugs (see Connecting technology)
Characteristics Combination of slip-on and heat shrinkable components, Wide cross-section range, Quick, safe and easy assembly, Ready for immediate operation
Applications Indoor
More Information
Voltage levels U0/U (Um) 12/20 (24) kV - 12,7/22 (24) kV
Test standards DIN VDE 0278-629-2
Length L 450 mm
Diameter over core insulation after removal of the outer conductive layer min 12,2 mm
Number of sheds per phase 1 Pieces
Diameter shed 80 mm
Nominal cross section 24 kV min 16 mm²
Nominal cross section 24 kV max 35 mm²
More Information
Delivery scope Conductive spreader cap, Heat shrinkable tube (tracking resistant), Conductive heat shrinkable tubes, Silicone sheds, Oil barrier tubing, Earthing wire, Pressure spring, Sealing tape, Oil-barrier field control filling tape (blue), Assembly instructions
Shelf life description Unlimited shelf life
Country of origin Germany
Customs tariff number 85469090
EAN/GTIN 4010311051031
Packaging type Piece Carton Pal. OW
Content quantity 1 1 42
Unit of measure Piece Piece Piece
Lenght (mm) 730 730 1200
Width (mm) 165 165 800
Height (mm) 157 157 1130
Net weight (kg) 1,359 1,359 57,078
Gross weight (kg) 1,696 1,696 75,278